CLOSE
150A AC Contactor

Product Parameters

Performance description

■ Covering the 115~800A rated current range, AC/DC coil control.
■ Both product types (standard type, special type) have the same size.
■ The contact wear condition can be read through the scale, which is convenient for product maintenance.
■ The reversible contactor can be installed vertically and horizontally.
■ Zero flashover design, high safety.
■ The special double-coil design ensures that the contactor can be opened and closed quickly, while saving a lot of     energy consumption.

Technical parameter

Type

 

HLF1-D115

HLF1-D150

HLF1-D185

HLF1-D1225

HLF1-D265

Rated operation current (A)

Ie max AC-3

115A

150A

185A

225A

265A

(Ue≤440V)

Ie max AC-1

200A

250A

275A

315A

350A

(θ≤40℃)

Rated operational voltage (V)

max

1000V

1000V

1000V

1000V

1000V

Main contacts (NO)

3P/4P

3P/4P

3P/4P

3P/4P

3P/4P

Rated operational power AC-3 (kW)

220/240V

30kW

40kW

55kW

63kW

75kW

380/400V

55kW

75kW

90kW

100kW

132kW

415V

59kW

80kW

100kW

110kW

140kW

440V

59kW

80kW

100kW

110kW

140kW

500V

75kW

90kW

110kW

129kW

160kW

660/690V

80kW

100kW

120kW

129kW

180kW

1000V

65kW

65kW

100kW

140kW

147kW

Rated short-time withstand current (θ≤40℃)

10 Secs

1100A

1200A

1500A

1800A

2200A

30 Secs

640A

700A

920A

1000A

1230A

1 Min

520A

600A

740A

850A

950A

3 Min

400A

450A

500A

560A

620A

10 Min

320A

350A

400A

440A

480A

Rated impulse withstand voltage

8kV

8kV

8kV

8kV

8kV

Conventional thermal current

200A

250A

275A

315A

350A

Tightening torque (N.m)

10 N.m

18 N.m

18 N.m

35 N.m

35 N.m

Connection Mining

Line size (mm2)

2

2

2

2

2

 

20x3

25x3

25x3

32x3

32x4

 

Cable with spliding

95

120

150

185

240

Operation voltage

Cable with connector

95

120

150

185

240

(θ≤40℃)

Screw Diameter

Φ6

Φ8

Φ8

Φ10

Φ10

SCPD

Model

RT16-2

RT16-2

RT16-3

RT16-3

RT16-3

Rated current (A)

250A

355A

425A

500A

630A

Dimension

image001