Applicable scope
■ Protection against fire hazard caused by insulation faults.
■ Protection against the effects of sinusoidal alternating earth fault currents.
■ Protection against indirect contacts and additional protection against direct contacts.
■ Switching and isolation function
■ Both Pin and Fork busbar connection
■ Protection against the effects of sinusoidal alternating earth fault currents.
■ Protection against indirect contacts and additional protection against direct contacts.
■ Switching and isolation function
■ Both Pin and Fork busbar connection
Technical parameter
Rated Current (In): |
16, 20, 25, 32, 40, 50, 63, 80, 100A |
Rated working voltage (Ue): |
230/240V, 400/415V |
Number of Pole: |
1P+N (2P), 3P+N (4P) |
Rated residual current: |
30mA, 100mA, 300mA |
Residual current characteristics: |
A, AC, G, S |
Rated frequency: |
50/60Hz |
Impulse withstand voltage (Uimp): |
6kV |
Rated insulated voltage (Ui): |
500VAC |
Rated short circuit Inc (kA): |
6kA, 10kA |
Rated making and breaking capacity: |
500A (In=25A, 40A) or 10In (In=63A, 80A, 100A) |
Mechanical endurance: |
20000 times |
Electrical endurance: |
10000 times |
Protection degree: |
IP20 |
Wiring temination: |
35mm2 |
Ambient temperature: |
-25℃ ~ + 55℃, 95% humidity |
Torque of screw: |
2.5Nm |
Standard: |
IEC/EN 61008-1 |